1900/3300V Three-Core, PVC Insulated, PVC Sheathed Armoured to BS 6346

Construction
Conductor :
Plain annealed copper
Insulation : Flame retardant PVC compound
Filler: PVC or Polypropylene yarn
Binder Tape: Polyester (mylar) tape
Bedding: Flame retardant PVC compound
Armouring: Steel wire armored
Sheath: Flame retardant PVC compound

Size of Conductor

Nominal Thickness of Insulation

STEEL WIRE ARMOURED (SWA) CABLE

Nominal Thickness of Bedding

Nominal Dia. of Armour Wire

Nominal Thickness of Sheath

Approx. Overall Diameter

Approx. Weight

mm2

mm

mm

mm

mm

mm

kg/km

16

2.2

1.0

1.6

1.8

30.3

1845

25

2.2

1.0

1.6

1.8

33.1

2120

35

2.2

1.0

1.6

1.9

32.1

2540

50

2.2

1.2

2.0

2.0

35.6

3315

70

2.2

1.2

2.0

2.1

38.9

4190

95

2.2

1.2

2.0

2.2

42.3

5220

120

2.2

1.4

2.5

2.3

46.6

6640

150

2.2

1.4

2.5

2.4

49.4

7650

185

2.2

1.4

2.5

2.5

52.8

9000

240

2.2

1.6

2.5

2.6

63.5

11720

300

2.4

1.6

2.5

2.8

70.0

14150

400

2.6

1.6

3.15

3.0

78.0

18175

website: www.caledonian-cables.com

email: sales@caledonian-cables.com